Number of i/o points 12 analog inputs
Input type 0..10V
Input resistance 10K
A/D converter V/f conversion with auto calibration
Resolution 13 bits (input modes with 0.1% accuracy)
11 bits (input modes with 0.5%/1% accuracy)
Temperature drift +-0.01%/°C of measuring range
Scan time 30ms..980ms, depends on input mode
Integration time 60ms/20ms, depends on input mode
Calibration reference 10.000V
Accuracy, scan time software selectable, depends on input mode
mode no.ch accuracy scan time integration time auto calibration
0 12 0.1% 980ms 60ms each cycle
1 12 0.5% 420ms 20ms each cycle
2 12 1% 360ms 20ms every 10 minutes
3 6 0.1% 560ms 60ms each cycle
4 6 0.5% 240ms 20ms each cycle
5 6 1% 180ms 20ms every 10 minutes
6 4 0.1% 420ms 60ms each cycle
7 4 0.5% 180ms 20ms each cycle
8 4 1% 120ms 20ms every 10 minutes
9 2 0.1% 280ms 60ms each cycle
10 2 0.5% 120ms 20ms each cycle
11 2 1% 60ms 20ms every 10 minutes
12 1 0.1% 210ms 60ms each cycle
13 1 0.5% 90ms 20ms each cycle
14 1 1% 30ms 20ms every 10 minutes
Power consumption 24V 50mA
Galvanic isolation beetwen digital and analog circuit
no isolation between chanels
IEX-2 baud rate 20, 50, 100, 250, 500kbps, auto selectable
Operation temperature 0..50°C, 0..85% rh non-condensing
Dimension 53x117x58mm
Weight 120g
Enclosure IP20
Level of ambient pollution 2
Technical specifications